The manifold changeover systems are designed specifically for the manifold connection, changeover and flow control of gases in continuous or batch manufacturing processes. The compact design allows easy installation and operation, whilst ensuring a high degree of safety to end users. High pressure gauges on each supply side are also added to show the pressure of each side. The manifold changeover systems are color-coded and labelled with gas-specific information. Alarm panels and contact gauges can be added on manifolds control system for audible and visual sign of low contents to alert end-user to replenish. Ideal Gas Changeover systems are manufactured in different configurations to suit installation and customer needed flowrate and pressure. Point of use regulators can be added downstream at the application for use with the high flow manifold. Safety relief valve/flashback arrestor systems can be added easily to the outlet of the line regulator to ensure maximum safety for the equipment downstream. We also offer custom design for control supply from bulk supplies or pipelines.

Simplex Centre Supply

High Pressure Dual Block Valve, for 2x Manifold Centre Supply with direct regulator connection with Safety Valve, Non-Return Valve, Pressure Gauge, Isolation Valve on Plat assembly

IGE SCS-HP-BR-01

Ar / O2 / N2 / CO2 / Mixed Gas / He / LPG

Inlet Pressure: 20 000kPa ; Inlet Pressure: 3500kPa Outlet Pressure: 0-1000kPa or 0-3000kPa

Allows single manifold supply while a reserve manifold on standby for swift changeover when the bank primary bank is finished. Similar to Simplex Right Supply but with double manifold headers on each side of the control system

Duplex Supply

Regulated Supply from each Manifold header, Manifold header Isolation Valves, Safety Valves, Non-Return Valves, Pressure Gauge & Main Isolation Valve

IGE DST-LP-BR-02

IGE DST-LP-SS-03

IGE DST-LP-CS-04

Ar / O2 / N2 / CO2 / Mixed Gas / He / LPG

Ar / O2 / N2 / CO2 / Mixed Gas / He / H2 / C2H2 / LPG

H2 / C2H2 / LPG

Inlet Pressure: 20 000kPa ; Inlet Pressure: 3500kPa Outlet Pressure: 0-1000kPa or 0-3000kPa

Similar to simplex centre supply but with regulated supply from each manifold header.

Semi-Automatic

Regulated Supply from each Manifold header, second stage regulator for supply to operating point, Safety Valves, Non-Return Valves, Pressure Gauge & Main Isolation Valve

IGE SAS-LP-BR-08

IGE SAS-LP-SS-09

IGE SAS-LP-CS-10

Ar / O2 / N2 / CO2 / Mixed Gas / He / LPG

Ar / O2 / N2 / CO2 / Mixed Gas / He / H2 / C2H2 / LPG

H2 / C2H2 / LPG

Inlet Pressure: 20 000kPa ; Inlet Pressure: 3500kPa Outlet Pressure: 0-1000kPa or 0-3000kPa

Similar to duplex supply but uses differential pressure between header regulators to enable automatic changeover from primary to reserve supply. Manifold bank with high pressure setting is the primary supply. Regulator settings must be adjusted when changeover happens.

Fully Automatic

Regulated Supply from each Manifold header, automatic Changeover block, Safety Valves, Non-Return Valves, Pressure Gauge & Main Isolation Valve

IGE FAS-LP-BR-11

IGE FAS-LP-SS-12

IGE FAS-LP-CS-13

Ar / O2 / N2 / CO2 / Mixed Gas / He / LPG

Ar / O2 / N2 / CO2 / Mixed Gas / He / H2 / C2H2 / LPG

H2 / C2H2 / LPG

Inlet Pressure: 20 000kPa ; Inlet Pressure: 3500kPa Outlet Pressure: 0-1000kPa or 0-3000kPa

Similar to Semi-automatic but with changeover block to allow changeover between banks without changing regulator settings. No need to change regulator settings when changeover happens.

Electronic Changeover

Regulated Supply from each Manifold header, Solenoid Valves, Pressure Switch Gauges, Safety Valves, Non-Return Valves, Pressure Gauge & Main Isolation Valve

IGE ECS-LP-CS-14

IGE ECS-LP-CS-15

IGE ECS-LP-CS-16

Ar / O2 / N2 / CO2 / Mixed Gas / He / LPG

Ar / O2 / N2 / CO2 / Mixed Gas / He / H2 / C2H2 / LPG

H2 / C2H2 / LPG

Inlet Pressure: 20 000kPa ; Inlet Pressure: 3500kPa Outlet Pressure: 0-1000kPa or 0-3000kPa

Uses Pressure switch gauges to sense bank with low pressure indicating low gas content and activates solenoid with full bank to open and empty bank to close. Control system runs with control panel with indication panel or telemetry to signal when a bank is empty.

Custom Control System

Equipment selected to meet custom design specifications for the application.

IGE CCS-17

Ar / O2 / N2 / CO2 / Mixed Gas / He / H2 / C2H2 / LPG

Custom

We offer range of solutions for various application. This control system design follows custom design process for non-standard applications.